Clash detection - ignoring ProvisionforVoid

Scheduled Pinned Locked Moved General Discussion
19 Posts 8 Posters 4.8k Views
  • Oldest to Newest
  • Newest to Oldest
  • Most Votes
Log in to reply
This topic has been deleted. Only users with topic management privileges can see it.
  • K Offline
    K Offline
    Kai
    wrote on last edited by
    #2

    just exclude openings in your ruleset

    1 Reply Last reply
    0
    • L Offline
      L Offline
      LariMatias
      wrote on last edited by
      #3

      Are you trying to exclude clashes from the results when having clash detection between Architecture and HVAC models? And you try to exclude the clashes where there is a void object in the very same place? In this case you just can’t exclude those void objects from the ruleset as written above, I believe.

      I have bypassed this problem with the help of classification. This is how I usually do it: First, have clash detection between HVAC and void objects. Second, make a classification in which one manually classify the void clashing HVAC objects as “clashes voids” (you can manually classify object using selection basket). Finally, make a clash detection between Architecture model and HVAC models and exclude the HVAC objects that are classified as “clashes voids”.

      To put it simply, the idea is to have void objects and HVAC clash and then take these clashed objects out of the ruleset that detects clashes between Architecture and HVAC models.

      I can provide pictures for you to make it more understandable if you want, just let me know. This is not fully automatic process and I would like to hear better solutions as well.

      1 Reply Last reply
      0
      • I Offline
        I Offline
        ibo
        wrote on last edited by
        #4

        interessting solution. can you provide the pictures?

        L 1 Reply Last reply
        1
        • T Offline
          T Offline
          tguere
          wrote on last edited by
          #5

          So my solution was, to use the “Fire Stopping Identity Rule” from the extension BIM Coordination +, here is a page where you can read how it functions: https://help.solibri.com/hc/en-us/articles/11926739630615-Fire-Stopping-Identity-Rule#UUID-fd5be8a9-272d-731b-b71d-360e0c952e3c

          1 Reply Last reply
          0
          • L Offline
            L Offline
            LariMatias
            replied to ibo on last edited by
            #6

            @ibo Hey!

            Sorry for the long wait. Yes, I could provide pictures. But I use Solibri in Finnish so it may not makes that much sense.

            Do you think it would still tell the necessary story?

            P 1 Reply Last reply
            0
            • Alex.JA Offline
              Alex.JA Offline
              Alex.J
              wrote on last edited by
              #7

              Just use a gatekeeper.
              https://help.solibri.com/hc/en-us/articles/4415773412247-Using-Gatekeeper-Rules-to-Filter-Components-into-Sub-Rules
              First clash HVAC with opening, then in the subrule check passed components and clash them with the architectural components

              1 Reply Last reply
              1
              • P Offline
                P Offline
                Protiimi_Johanna
                wrote on last edited by
                #8

                I’ve been trying to achieve this, but not successful. Individually the rules I’ve created (HVAC vs opening and HVAC vs architectural components) seem to be working well. But how to achieve the result, where I can find only the clashes between HVAC and architectural, that don’t have opening defined? Now, to be clear, the model I’m using, does have problems (clashes without openings) with it.
                I’ve tried:
                -HVAC vs architectural as parent rule, check passed components (result: HVAC components that do clash openings)
                -HVAC vs opening as parent rule, check passed components (no results)
                -HVAC vs architectural as parent rule, check non-passed components (result: some HVAC components that do clash openings)
                -HVAC vs opening as parent rule, check non-passed components (no results)

                I wouls say that using a gatekeeper rule doesn’t give wanted results. Or I just can’t figure out how to do it.

                Alex.JA 1 Reply Last reply
                0
                • P Offline
                  P Offline
                  Protiimi_Johanna
                  replied to LariMatias on last edited by
                  #9

                  @LariMatias
                  I’m also a Finnish user, and would be interested in your solution, if you can provide more information!

                  1 Reply Last reply
                  0
                  • L Offline
                    L Offline
                    LariMatias
                    wrote on last edited by LariMatias
                    #10

                    I’ve tried the gatekeeper / parent rule solution some time ago with no success, but I will need to check Alex’s link.

                    Anyway, here is a loose guide for how I do it:

                    1. I check HVAC which is inside the hole reservation objects / openings with Solibri common rule SOL/234/1.2 (in the parameter of the ruleset I use an automated classification to determine the objects for the check, but you can use certain models for example to determine the HVAC components and hole reservation components):
                      220a3129-5b79-4379-b1bb-8393d6dd0dab-kuva.png

                    The result brings me every HVAC component that is somehow inside a hole resevation / an opening. It also brings me all the hole reservations.

                    1. I create a manual classification from the results of the former clash detection. I insert “TATE, joka on reikävarauksen sisällä” for the HVAC components (and “Reikävaraus, jonka sisällä on TATE” for the hole resevation components).

                    (This is the trickiest part, I think:) To do that I manipulate the “selection basket” to include only the HVAC components by choosing all the uncleared components from the clash detection and then subtract all hole reservations with model tree. Then I manually set them the right classification. The picture here shows the results of the classified components but you should firstly use the unclassified components tab and the option to show only components that are in the selection basket:
                    3719ce23-ca85-4b15-ba22-6caf1ec5cc92-kuva.png

                    1. Now I should have a classification for the HVAC components that are located inside hole reservations / openings. I can then subtract them from the clash detection (SOL/1/5.1) between structural/architectural components and HVAC components:
                      6a658f5c-ce72-41a8-b3f2-03fc7d4d7faa-kuva.png

                    Hope you find some logic in this and let me know if there something missing, I try to explain better then.

                    EDIT: Grammar + added some extra information to the 2nd part.

                    1 Reply Last reply
                    1
                    • Alex.JA Offline
                      Alex.JA Offline
                      Alex.J
                      replied to Protiimi_Johanna on last edited by
                      #11

                      @Protiimi_Johanna said in Clash detection - ignoring ProvisionforVoid:

                      -HVAC vs opening as parent rule, check passed components (no results)

                      This is indeed how I use it. The “openings” are modelled provisions for void as IfcBuildingElementProxy though, not IfcOpeningElements. Of course it is important that the PFV are in the right filter, as the components passed by the gatekeeper to the subrule are those from the left filter. Thus HVAC needs to be on the left.

                      @LariMatias said in Clash detection - ignoring ProvisionforVoid:

                      I’ve tried the gatekeeper / parent rule solution some time ago with no success

                      I’d be interested to know what the issue was.
                      It is true that we don’t verify the placement of HVAC within the PFV, this is done by another subsequent rule which doesn’t work perfectly.

                      We have seen custom rules from some Solibri resellers that might yield better results, but weren’t able to test them in detail as of today. I’ll post some more information when we’ll get to it.

                      1 Reply Last reply
                      1
                      • P Offline
                        P Offline
                        Protiimi_Johanna
                        wrote on last edited by
                        #12

                        I don’t get it. I started over, but I can’t make it work.

                        1 Reply Last reply
                        0
                        • sarahhielscherS Offline
                          sarahhielscherS Offline
                          sarahhielscher
                          wrote on last edited by
                          #13

                          Did you try rule SUK 1017 from the free BIM Coordination + Extension for this?
                          It is able to check different scenarios with and without a PfV and/or an existing opening

                          Alex.JA 1 Reply Last reply
                          0
                          • Alex.JA Offline
                            Alex.JA Offline
                            Alex.J
                            wrote on last edited by
                            #14

                            Gatekeeper rule:
                            dca8a28d-b7e7-4f27-89c2-001662bdeaa1-image.png

                            Sub-rule:
                            1edee6a3-96ee-468e-a15a-52b9ee0be2a6-image.png
                            Note that we could have all MEP disciplines in one sub-rule, but we preferred having one sub-rule per MEP-discipline.

                            RESULT:
                            Step 1: all MEP components that do not clash with a Provision for Void are passed to the sub-rule
                            Step 2: from those passed components, we select one specific discipline per sub-rule and check for clashes with the structure.

                            Limitations: the MEP components could clash with the PFV without being centered, and without having the correct distance. This is checked in a separate rule down the road.
                            Our rule #0702 (this includes Gatekeeper + subrule) merely checks if there is a PFV request for each MEP component clashing with a structural component. The other rule will check the dimensions of the PFV.

                            Does that help @Protiimi_Johanna ?

                            L P 2 Replies Last reply
                            1
                            • Alex.JA Offline
                              Alex.JA Offline
                              Alex.J
                              replied to sarahhielscher on last edited by Alex.J
                              #15

                              @sarahhielscher I think that’s the one we quickly tested.
                              If I remember correctly, we felt that the prerequisites might be a bit too restrictive in our case - but I’m still interested to dig further.

                              EDIT: here’s the link https://help.solibri.com/hc/en-us/articles/15129074179351-Update-Log-for-BIM-Coordination-Extension

                              E 1 Reply Last reply
                              0
                              • E Offline
                                E Offline
                                EloyRD
                                replied to Alex.J on last edited by
                                #16

                                @Alex-J could you share wich rule are you using to check that there is enough distance betwenn the pipe / duct / cable tray and the border of the opening?
                                I am having trouble finding a solution that is consistent.

                                1 Reply Last reply
                                0
                                • P Protiimi_Johanna referenced this topic on
                                • L Offline
                                  L Offline
                                  LariMatias
                                  replied to Alex.J on last edited by
                                  #17

                                  @Alex-J Thanks for the tips! I tried it now with simple enough setup and got it working! So, as a result, I have HVAC+E that clashes with STR where there is no ProvisionForVoid at “exact” same location.

                                  I think my problem earlier was, that I had PfVs included somewhere in clash rule they were not supppose to be.

                                  Also, I edited the gatekeeper rule the way that it doesn’t check for clashes but rather component inside another: HVAC+E components as inner components and PfV as outer components. I don’t know if it’s any different but maybe it’s a bit more adjustable than clash checking.

                                  1 Reply Last reply
                                  0
                                  • Alex.JA Offline
                                    Alex.JA Offline
                                    Alex.J
                                    wrote on last edited by Alex.J
                                    #18

                                    @LariMatias said in Clash detection - ignoring ProvisionforVoid:

                                    Also, I edited the gatekeeper rule the way that it doesn’t check for clashes but rather component inside another: HVAC+E components as inner components and PfV as outer components. I don’t know if it’s any different but maybe it’s a bit more adjustable than clash checking.

                                    Is that working well? I always assumed that if the pipe was longer than the wall (and PFV) thickness, this would not work. The orientation of the PFV, specifically cubic ones seems to be to complex to take into account… I’d happy to have some more feedback!

                                    @EloyRD sorry for the late reply, I haven’t dived into rule administration for some time now, I’ll try to find some time soon. But basically yes, we have the same difficulties to find a rule that gives consistent results. We probably tried out at least 6 different ways… I think the custom rules mentioned above by @sarahhielscher are using a better JavaScript code, you might be interested to try them out. Here’s the link: https://help.solibri.com/hc/en-us/articles/29123641190807-Fire-Stopping-Advanced-Identity-Rule

                                    1 Reply Last reply
                                    0
                                    • P Offline
                                      P Offline
                                      Protiimi_Johanna
                                      replied to Alex.J on last edited by
                                      #19

                                      @Alex-J Now I had finally time to return to this rule. Turns out the problem was that I had the MEP as the component 2 (the wrong side). I had never thought that the positioning of the checked components is significant.
                                      Thanks a lot, now I (once again) feel like I can do anything!

                                      1 Reply Last reply
                                      1